Inspection History: GRADING - INTERMEDIATE

Permit Number - T04BU01059

Inspection Description - GRADING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/26/2007 GRADING - INTERMEDIATE Approved SEE NOTES FOR FINAL GRADING
10/25/2007 GRADING - INTERMEDIATE Partial Approval FINAL GRADING INSPECTION IN PROGRESS
10/11/2007 GRADING - INTERMEDIATE Partial Approval FINAL GRADING INSPECTION IN PROGRESS
06/22/2006 GRADING - INTERMEDIATE Correction Required STANDING WATER EAST OF COURTLAND DRIVE
STANDING WATER AT STARLING AND PAINTED TURTLE IN RIP RAP AREA
CALLED BURT AND ADVISED
SHOWED JAIME ON SITE DRAINAGEWAY ALONG COURTLAND HOLDING WATER AND EROSION FROM DOWNSPOUTS
05/09/2006 GRADING - INTERMEDIATE Correction Required Civano II
T04BU01059
10411 E. Bilby Rd.

Preliminary Punch List Only

Clear all debris/silt in 24" RCP stormdrain pipes.

Clean up all concrete debris in ROW between Sidewalk and Road.

Install all low voltage lighting (keynote #31) at ends of arbor walks.

Basin #4-
Southwest corner removable post barricade has been cemented, broken ramp wing.
Southeast corner sidewalk is 3'3"(ADA compliance as well as COT Standard), broken ramp wing.
I am unable to verify filter fabric under scupper splash pads.
Clean out silt and debris from scuppers.
All improvements to basin (basketball court, walking paths, additional drainage pipes) not shown on grading plans. I am in the process of verifying with COT reviewer how this is to be handled.

Basin #3- build weir to plan, install 6" low flow pipe to off site drainage per plan, grade basin to drain (build to plan elevations).

Channel #3- build to plan, match side slopes and depth.

Complete all site stabilization. Once all stabilization (and construction) has been completed all SWPPP Controls need to be removed.

24" RCP at north end of Swaying Palms Dr needs to be cleaned (silt removed) and silting at splash pad needs to be addressed.
05/08/2006 GRADING - INTERMEDIATE Correction Required INSPECTING FOR PUNCHLIST
05/04/2006 GRADING - INTERMEDIATE Correction Required INSPECTING FOR PUNCHLIST