Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA PRE-GUNITE
Permit Number - T04BU00938
Inspection Description - POOL/SPA PRE-GUNITE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2004 | POOL/SPA PRE-GUNITE | Approved | IVRS - Inspection :* | |
| 06/03/2004 | POOL/SPA PRE-GUNITE | Not ready for Inspection | IVRS - Inspection :*/ 1) CANNOT UNDERSTAND STRUCTUAL DRAWINGS, SOIL TYPE OR REBAR CHARTS | |
| 05/26/2004 | POOL/SPA PRE-GUNITE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) DETAIL Q OF PLAN AZ-P NOT COMPLIED WITH 2) ALTERNATE REINFORCEMENT BARS NOT INSTALLED. SEE SCHEDULE FOR 8 FT POOL 3) ELECTRIC SUB PANEL MUST HAVE AN ISOLATED NEUTRAL BAR 4) PROVIDE SOIL ANALYSIS OR BUILD TO WORSE CASE BASIS |