Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2005 | FIRE SPKLR - FINAL | Approved | ||
| 01/07/2005 | FIRE SPKLR - FINAL | Not ready for Inspection | 1.) Alarm bell shall be on a separate, dedicated circuit can not wire to closet light. 2.) Label panel for alarm circuit, and install a lock out on breaker. 3.) Turn up time on bell to activated at 30 sec. to 90 sec. |