Permit: T04BU00760

Parcel: 14042036A


Addresses:

2450 E VALENCIA RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04BU00760

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/26/2004 ELECTRIC - FINAL Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
04/22/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) CONDUIT DEPTH AT DISPENSER TO BE 2' PER NEC AND NOTE 2 OF APPROVED PLANS. 2) REPLACE CONCRETE COVER, BROKEN, DOES NOT SEAL U.G. BOX OPENING, PIPES LAYING BY BOX. 3) REMOVE SEAL-OFF PLUGS AT DISPENSER AREA TO VERIFY COMPOUND SEAL. 4) RESEAL SEAL-OFF FITTING BELOW GUTTER IN ELECTRIC ROOM. 5) BOND BUSHING REQUIRED AT CONDUIT TERMINATION IN GUTTER, BOND TO ENCLOSURE AND EQUIP. GROUND. 6) USE LISTED 2 POLE BREAKER FOR DISPENSER POWER IN PANEL 'A' - 2 SINGLE POLE BREAKERS WITH BENT WIRE BETWEEN HANDLES NOT APPROVED.
04/16/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ NOTES: 1) NEED APPROVED PLANS/PERMIT ON SITE. 2) SEAL OFF REQUIRED WITHIN 18" OF J-BOX. 3) SIGN REQUIRED FOR EM. SHUT OFF LOCATION.