Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04BU00760
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
04/22/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) CONDUIT DEPTH AT DISPENSER TO BE 2' PER NEC AND NOTE 2 OF APPROVED PLANS. 2) REPLACE CONCRETE COVER, BROKEN, DOES NOT SEAL U.G. BOX OPENING, PIPES LAYING BY BOX. 3) REMOVE SEAL-OFF PLUGS AT DISPENSER AREA TO VERIFY COMPOUND SEAL. 4) RESEAL SEAL-OFF FITTING BELOW GUTTER IN ELECTRIC ROOM. 5) BOND BUSHING REQUIRED AT CONDUIT TERMINATION IN GUTTER, BOND TO ENCLOSURE AND EQUIP. GROUND. 6) USE LISTED 2 POLE BREAKER FOR DISPENSER POWER IN PANEL 'A' - 2 SINGLE POLE BREAKERS WITH BENT WIRE BETWEEN HANDLES NOT APPROVED. |
|
04/16/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ NOTES: 1) NEED APPROVED PLANS/PERMIT ON SITE. 2) SEAL OFF REQUIRED WITHIN 18" OF J-BOX. 3) SIGN REQUIRED FOR EM. SHUT OFF LOCATION. |