Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2004 | FIRE SPKLR - FINAL | Approved | ||
| 06/25/2004 | FIRE SPKLR - FINAL | Denied | 1. Change fire sprinkler in utility room. Painted/loaded with stucco. 2. Relocate sprinkler in Corridor 127. 3. Provide escutcheons where missing. 4. Provide spare head box, sprinkler heads & wrench. 5. Cannot final until underground piping flush is completed. |