Inspection Status: Violation
Inspection History: INITIAL CODE VIOLATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2003 | INITIAL CODE VIOLATION | Violation | EMERGENCY CALLOUT - ELECTRICAL FIRE N&O SIGNED BY OWNER SOUTHWESTERN WORK SHOP CEILING AREA, APPERAS AN ELECTRICAL CIRCUIT INSIDE WALL CLOSE TO CEILING SHORTED AND BURNED 1/" EMT CONDUIT STARTING SMALL FIRE IN WALL, TFD OPENED SMOKING WALL TO PUT OUT FIRE. TEP CALLED TO LOCKOUT SERVICES, TWO OTHER ELECTRICAL CIRCUITS IN AREA BURNED. REMARKS: OWNER TO OBTAIN SERVICES OF LICENSED ELECTRICAL CONTRACTOR TO SECURE A 1 HOUR REPAIR PERMIT TO REPAIR 3 CIRCUITS THEN CALL FOR INSPECTION AND RE-ENERGIZE SERVICE. F/U 08/01/03 |
|
| 07/26/2003 | INITIAL CODE VIOLATION | Violation | DAMAGE REPORT: LOCATION: SOUTH WEST SHOP AREA, NORTH DOOR CEILING WALL AREA; BUILDING: BURNED FRAMING AROUND CONDUIT AREA, TFD OPENED ROOF SECTION TO EXPOSE FIRE; ELECTRICAL: THREE CIRCUITS NEED TO BE REPAIRD 1/2" CONDUIT BURNED APART, ELECTRICIAN TO CHECK ENTIRE CIRCUITS AND REPAIR. AN ELECTRICAL PERMIT BY ELECTRICAL CONTRACTOR FOR 1 HOUR REPAIR REQUIRED, AND AFTER INSPECTION POWER CAN BE RELEASED. ELECTRICAL CONTRACTOR TO TERMINATE GROUND WIRE IN MAIN PANEL LEFT HANGING LOOSE. |