Inspection Status: Violation

Inspection History: INITIAL CODE VIOLATION

Case Number - T03VL00696

Inspection Description - INITIAL CODE VIOLATION

Inspection Status - Violation

Date Description Inspector Results Comments
10/08/2003 INITIAL CODE VIOLATION Violation A PERMIT IS REQUIRED FOR ELECTRICAL WORK
07/23/2003 INITIAL CODE VIOLATION Violation EMERGENCY CALLOUT - ELECTRICAL FIRE
N&O INDEMNIFICATION NOT SIGNED.
RECEPTACLE WIRED IN ZIP CORD BURNED AND CHARRED AREA ROUND IT ON WALL, CIRCUIT REMAINED ENERGIZED, COULD NOT LOCATE SUBPANEL. OWNER CLAIMS SUBPANEL LOCATED IN LOCKED ROOM USED FOR STORAGE - COULD NOT FIND KEY. SINCE CIRCUIT COULD NOT BE LOCATED AT ORIGIN AND SHUT OFF, INSPECTOR LOCKED MAIN 40 AMP CB. OCCUPANT TO BE RELOCATED THRU RED CROSS.
REMARKS: OWNER WILL HAVE TO OBTAIN ELECTRICAL CONTRACTOR TO REMOVE ALL ZIP CORDS AND EXTENSION CORDS USED PERMANENTLY AND INSTALL PERMANENT RECEPTACLES IN ALL ROOMS. PERMOT FOR ELECTRICAL WORK REQUIRED. F/U 07/25/03
07/23/2003 INITIAL CODE VIOLATION Violation DAMAGE REPORT:
LOCATION: EAST WALL, EAST BEDROOM;
BUILDING: NONE
ELECTRICAL: WALL RECEPTACLES WIRED IN ZIP CORD, ONE OUTLET BURNED, THE WIRE FEEDING IT WAS STILL HOT, LOOKED FOR SUBPANEL COULD NOT LOCATE, OWNER CLAIMS PANEL IN LOCKED ROOM FULL OF STORAGE.
PLUMBING: NONE
MECHANICAL: NONE
SUMMARY: COULD NOT ISOLATE HOT CIRCUIT, INSPECTOR LOCKED SERVICE TILL ELECTRICIAN CAN LOCATE SUBPANEL AND ISOLATE CIRCUIT. WIRING THRU OUT UNIT USING ZIP CORD. ALL ZIP CORD AND EXTENSION CORD WIRING TO BE REMOVED AND SUFFICIENT PERMANENT RECEPTACLES TO BE INSTALLED. F/U 07/25/03