Case: T03VL00647

Parcel: 106062980


Addresses:

902 W THURBER ST

Inspection Status: Violation

Inspection History: INITIAL CODE VIOLATION

Date Description Inspector Results Comments
07/08/2003 INITIAL CODE VIOLATION Violation EMERGENCY CALLOUT - ELECTRICAL - CALLOUT BY TFD
CALLED OUT BY FIRE DEPT TO CHECK ELECTRICAL PROBLEM, OCCUPANTS SMELLED A FIRE TYPE ODOR AND LIGHT SMOKE HAZE AT EAST BEDROOM SIDE OF HOUSE. WHEN ENGINE 8, CAPT ADAMS, ARRIVED ON SITE ALSO NOTICED ODOR AND SMOKE HAZE. WHEN INSPECTOR ARRIVED, ODOR WAS ALSO NOTICED AND HAZE HAD GONE. FOURD BEDROOM 15 AMP CIRCUIT BREAKER NOT WORKING AND NO PWOER, AFTER REST, TOOK VOLTAGES ON VARIOUS RECEPTACLES IN BEDROOMS AND SUB-PANEL IN HALL CLOSET AND FOUND FLUCTUATING VOLTAGES OF 129V-159V. DECISION TO LOCK OUT SERVICE PANEL MADE UNTIL OWNER OBTAINS SERVICE OF LICENSED ELECTRICAL CONTRACTOR TO CORRECT PROBLEMS. F/U 07/11/03
07/08/2003 INITIAL CODE VIOLATION Violation DAMAGE REPORT: THE SMELL OF BURNING AND LIGHT HAZE MADE OCCUPANTS CALL TFD.
INSPECTOR WAS CALLED OUT TO CHECK ELECTRICAL AND FOUND BEDROOM BREAKER NOT WORKING ALSO NOTICED VOLTAGE FLUCTUATING FROM 129 TO 159 VOLTS. OCCUPANT TO RELOCATE TONITE UNTIL OWNER OBTAINS LICENSED ELECTRICAL CONTRACTOR TO REVIEW ELECTRICAL PROBLEM, SERVICE PANEL LOCKED OUT BY INSPECTOR. ELECTRICIAN TO CONTACT INSPECTOR TO UNLOCK.