Inspection History Details
Inspection Status: Correction Required
Inspection History: INITIAL CODE VIOLATION
Case Number - T03VL00475
Inspection Description - INITIAL CODE VIOLATION
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2003 | INITIAL CODE VIOLATION | Correction Required | CITY OF TUCSON FACILITIES TO PULL OUT MAIN BREAKER TO GENERATOR AT SWITCH GREAR TO ISOLATE GENERATOR FROM BACK FEED OF UTILITIES POWER. WILL CLOSE TIE BREAKER TO RE ENERGIZE LOCAL PLANT OPERATION. CAUSE OF DAMAGE: FIRE IN MECH. RM. GENERATOR CAUGHT ON FIRE. BUILDING: SMOKE DAMAGE: ELECTRICAL: CONTROL WIRING DAMGED BY FIRE ABOVE GENERATOR FOR GEN. CONTROLS. MECHANICAL SMOKE DAMAGE, DAMAGE TO AIR FILTERS ON GENERATOR. SUMMARY OF REMARKS: AIR INTAKE FILTERS STARTED FIRE DUE TO BACKFIRE WHEN GEN. STARTED. TUCSON DISTRICT ENERGY UNDER CONTRACT TO MAINTAIN SYSTEM WILL MAKE NEC. REPAIRS ASAP TO BRING GEN. BACK ON LINE. TUCSON DISTRICT ENERGY LC. PO. BOX 53901 PHOENIX AZ 85072-3901. F.U. 6/2/03 |