Inspection History Details
Inspection Status: Correction Required
Inspection History: INITIAL CODE VIOLATION
Case Number - T03VL00289
Inspection Description - INITIAL CODE VIOLATION
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/03/2003 | INITIAL CODE VIOLATION | Correction Required | ISSUED MAINTENANCE REPRESENTATIVE A COPY OFF DAMAGE REPORT AND NOTICE AND ORDER. ELECT SERVICE LOCKED OUT BY BRAD JENNING MAINT DEPT. ELECT CONTRACTOR TO VERIFY AND DRY OUT ELECT PANEL ALL FIXTURES, AND ELECT SW'S AND OUTLETS. CAUSE OF DAMAGE: BROKEN WATER CONNECTION TO TOILET FIXTURE ON 2ND FLOOR, WATER RAN ONTO FLOOR AND DOWN. LOCATION OF DAMAGE: WALLS TO UNIT 9109. BUILDING: SHEET ROCK DAMAGE 9101 CIELING AREAS BATHROOM AND BED ROOM AND LIVING & KIT RMS. ELECTRICAL: ELECT PANEL WET VARIOUS RECEPTS AND SWITCHES WET, DC ALARMS WET. ELECTRICAL CONTRACTOR TO BE OBTAINED TO DRY OUT ALL ELECT IN UNIT. PLUMBING: DIAMETER DAMAGED LINE REPAIR TO TOILET BY MAINT DEPT NO PERMIT REQUIRED. MECHANICAL:NONE SUMMARY OF REMARK OBTAIN A PERMIT AT OUT OFFICE FOR STRUCTURAL RPAIR REINSTALL SHEET ROCK, ALSO A PERMIT FOR A 1 HR INSPECTION PRIOR TO OCCUPANCY. BRAD JENNINGS HAS LOCKED OUT MAIN ELECT UNTIL ELECT CONTRACTOR CORRECTS PROBLEMS OCCUPANCYS TO STAY OUT TILL REPAIRS MADE ON SITE MAINTENANCE TO STANDBY BUILDING TILL FIRE ALARM PANEL CORRECTED. FOLLOW UP 4/3/03 |