Permit: T03PL02161

Parcel: 11714215B


Addresses:

531 S RUSSELL AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03PL02161

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ CORRECTIONS MADE OK. UCC LEFT AT METER. S.W. GAS 889-1888
12/30/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) MUST REMOVE UNIONS IN LINE NEW AND EXISTING AND REPLACE WITH RIGHT AND LEFT HAND NIPPLES. 2) MUST PROVIDE AN ENCLOSURE FOR WTR HTR WHEN LOCATED OUTDOORS. 3) MUST REPLACE T&P VALVE AND PROVIDE A DRAIN AND TERMINATE 6" A.F.F. 4) RE-TEST SYSTEM - 10 LBS MIN.