Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/12/2003 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) LEFT GAS CARD |
| 12/11/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ USE A REDUCER FITTING WHERE 3" VENT CONNECTS INTO 4" VENT OR REPLACE 4" WITH 3". PROVIDE A MIN. 1" CLEARANCE FROM COMBUSTABLES. |
| 12/08/2003 |
PLUMBING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK. 2) OK TO BACKFILL TRENCH. 3) MUST REPLACE SHUT OFF VALVE @ WTR HTR WITH AGA OR CSA APPROVED VALVE. 4) MUST SCREW DOWN WTR HTR FLU VENTS WITH [3] SHEET METAL SCREWS PER JOINT. 5) MUST EXTEND DBL WALL FLU VENT AT LEAST 6" PAST WOOD RAFTER THEN CONNECT SINGLE WALL VENT CONNECTOR. 6) MUST EXTEND DBL WALL FLU 3'0" ABOVE COOLER WITH FLU CAP. 7) MUST EXTEND T&P RELIEF DRAIN TO OUTSIDE TERMINATE 6" A.F.F. |