Inspection History: PLUMBING - FINAL

Permit Number - T03PL02038

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/12/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 1) LEFT GAS CARD
12/11/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ USE A REDUCER FITTING WHERE 3" VENT CONNECTS INTO 4" VENT OR REPLACE 4" WITH 3". PROVIDE A MIN. 1" CLEARANCE FROM COMBUSTABLES.
12/08/2003 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK. 2) OK TO BACKFILL TRENCH. 3) MUST REPLACE SHUT OFF VALVE @ WTR HTR WITH AGA OR CSA APPROVED VALVE. 4) MUST SCREW DOWN WTR HTR FLU VENTS WITH [3] SHEET METAL SCREWS PER JOINT. 5) MUST EXTEND DBL WALL FLU VENT AT LEAST 6" PAST WOOD RAFTER THEN CONNECT SINGLE WALL VENT CONNECTOR. 6) MUST EXTEND DBL WALL FLU 3'0" ABOVE COOLER WITH FLU CAP. 7) MUST EXTEND T&P RELIEF DRAIN TO OUTSIDE TERMINATE 6" A.F.F.