Permit: T03PL02005

Parcel: 119032770


Addresses:

711 W 41ST ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/05/2003 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK. 2) ALL CORRECTIONS HAVE BEEN MADE.
12/03/2003 PLUMBING - GAS PRESSURE TEST Denied 1) MUST INSTALL GAS SHUT OFF VALVE, THEN UNION OR REMOVE UNION AND INSTALL RIGHT AND LEFT HAND NIPPLE 2) MUST APPLY TAPE PRIMER AND 10 MIL TAPE TO EXISTING GAS LINE IN FRONT OF HOUSE 3) WILL REQUIRE A VARIENCE FORM FOR ALTERNATE METHOD OF INSTALLATION OF T & P VALVE 4) REMOVE WOOD BASE UNDER WATER HEATER AND INSTALL CONCRETE BASE 5) RE-TEST THE SYSTEM 10 POUNDS MINIMUM