Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/03/2003 |
PLUMBING - FINAL |
|
Approved |
1) GAS PRESSURE TEST IS OK 2) WATER HEATER FLUE VENT, T & P, VALVE AND DRAIN OK 3) GAS PACK ON ROOF IS OK 4) OK TO BACKFILL TRENCH |
| 12/02/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) GAS PRESSURE TEST WAS BELOW 10 LBS MIN. 2) MUST REMOVE FLEX LINE ON T&P DRAIN AND RUN FULL SIZE 3/4" DRAIN. 3) MUST PROVIDE ANOTHER 10X10 LOUVER GRILL ON WATER HTR DOOR 12" BELOW CEILING. 4) MUST SEAL GAS LINE PENETRATION AT REAR OF HOUSE. |