Permit: T03PL01983

Parcel: 121111460


Addresses:

4762 E ADAMS ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
12/05/2003 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection 0000*/ 19 PSI TEST OK. ALL CORRECTIONS HAVE BEEN MADE. LEFT GAS CARD.
12/03/2003 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection 0999*/ 1) PROVIDE MIN. 1" CLEARANCE AROUND WATER HEATER VENT AT ROOF PENETRATION. 2) EXTEND GAS PIPE ALL THE WAY TO STOVE. 3) CLAMP GAS PIPE TO BLOCKS ON ROOF. 4) PRESSURE GUAGE DOES NOT WORK. NO PRESSURE IN LINE BUT GUAGE STILL READS 22 LBS. RECALL FOR INSPECTION.