Inspection History: PLUMBING - FINAL
Permit Number - T03PL01842
Inspection Description - PLUMBING - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) DOUBLE WALL SHALL BE USED AT PENETRATION OF ROOF WITH ROOF FLASHING AND APPROVED CAP OR PROVIDE 6" CLEARNACE FOR SINGLE WALL FROM COMBUSTIBLES WITH ROOF FLASHING AND APPROVED CAP | |
12/02/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ 1) PROVIDE MIN. 3 SCREWS IN WTR HTR VENT EACH JOINT. 2) EXTEND VENT 3' ABOVE EVAP COOLER. USE DOUBLE WALL VENT PIPE. 3) PROVIDE HIGH AND LOW COMBUSTION AIR VENTS MIN. 100 SQ. IN. EACH OPENING. |