Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03PL01842

Parcel: 106090240

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Permit Number - T03PL01842

Inspection Description - PLUMBING - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
01/08/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) DOUBLE WALL SHALL BE USED AT PENETRATION OF ROOF WITH ROOF FLASHING AND APPROVED CAP OR PROVIDE 6" CLEARNACE FOR SINGLE WALL FROM COMBUSTIBLES WITH ROOF FLASHING AND APPROVED CAP
12/02/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) PROVIDE MIN. 3 SCREWS IN WTR HTR VENT EACH JOINT. 2) EXTEND VENT 3' ABOVE EVAP COOLER. USE DOUBLE WALL VENT PIPE. 3) PROVIDE HIGH AND LOW COMBUSTION AIR VENTS MIN. 100 SQ. IN. EACH OPENING.