Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/24/2003 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ CORRECTIONS HAVE BEEN MADE. CARD AT METER SET. CALL GAS CO. 889-1888 |
| 11/13/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ SEE ITEM #6 ON INSPECTION DATED 10/30/03 ALSO GAS PIPING TO BE SECURED USING APPROVED FASTENING DEVICES. ALL GAS VALVES TO BE CSA OR AGA APPROVED. |
| 10/30/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) 10 PSI PRESSURE TEST COMPLETE GAS SYSTEM. 2) ALL ABOVE GROUND GAS PIPING SHALL BE MIN. 6" ABOVE FINISHED GRADE. 3) NO UNIONS SHALL BE ALLOWED IN LINE PIPING. 4) PLEASE PROVIDE WATER HEATER PERMIT. 5) WATER HEATER T&P SHALL GRAVITY DRAIN TO DAYLIGHT. 6) CONTRACTOR TO PROVIDE GAS ISOMETRIC FOR NEW GAS SYSTEM. 7) CONTRACTOR SHALL PROVIDE PROPER WATER HEATER VENT TERMINATION. 8) WATER HEATER SHALL HAVE UNIONS ON PIPING WITHIN 12" OF APPLIANCE. |