Permit: T03PL01794

Parcel: 133042440

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/21/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ APPEAL ON LOB - # 2003-105. CORRECTIONS HAVE BEEN MADE.
10/31/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) CONTRACTOR TO PROVIDE PETITION OF APPEAL FORM AT RESIDENCE FOR ALTERNATE FORM OF T&P RELIEF. 2) CONTRACTOR TO SEE SEC. 605.3 FULLWAY VALVE REQUIRED AT DISCHARGE SIDE OF EACH WATER METER. PER 94 UPC.
10/30/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) HOT AND COLD PIPING AT WASHING MACHINE MUST BE ISOLATED FROM EACH OTHER. 2) WATER HEATER T&P DRAIN MUST GRAVITY FLOW TO DAYLIGHT. 3) SEC. 605.1 WATER HEATER SHALL HAVE A FULL WAY VALVE ON DISCHARGE SIDE. 4) 10' OF COPPER IS REQUIRED AT SERVICE FOR PROPER GROUNDING OF ELECTRIC WITH GROUND CLAMP REATTACHED.