Permit: T03PL01740

Parcel: 116171640


Addresses:

1012 W ONTARIO ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/02/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*
01/29/2004 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) REQUIRED COMBUSTION RELIEF IN UPPER AND LOWER 12" OF ENCLOSURE. 2) SINGLE WALL VENT CONNECTOR REQUIRE 6" CLEARANCE FROM COMBUSTABLES. 3) EXTEND T&P RELIEF DRAIN WITH APPROVED MATERIALS. 4) PRESSURE TEST OK.