Permit: T03PL01737

Parcel: 130031420


Addresses:

2606 E KESWICK CI

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/31/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ ALL CORRECTIONS MADE. 10 PSI PRESSURE TEST OK FROM METER TO WATER HEATER, WALL HEATER, FURNACE. CONTRACTOR TO BACKFILL AND COMPACT PROPERLY UNDER PIPING AFTER ELECTRIC GOES IN. GAS CARD DROPPED AT METER.
10/30/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 10 PSI GAS PRESSURE TEST NOT HOLDING.
10/29/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 10 PSI GAS TEST IS OK FROM METER TO HOUSE. 1) ALL ABOVE GROUND PIPING SHALL BE MIN. 6" ABOVE FINISHED GRADE. 2) NO UNIONS SHALL BE ALLOWED IN LINE PIPING. RIGHT - LEFT NIPPLES AND COUPLINGS SHALL BE USED. 3) TIE HOSE PIPING INTO LINE FROM METER AND RETEST ENTIRE SYSTEM TO 10 PSI MIN. 4) ALL VALVES SHALL BE CSA OR AGA APPROVED RATED VALVES. 5) EXTEND FURNACE VENT 3' VERTICAL ABOVE COOLER. 6) EXTEND WATER HEATER T&P DRAIN DOWN TO WITHIN 6" OF FINISH GRADE WITH NO THREADS ON END.