Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/28/2003 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 10 PSI GAS PRESSURE TEST IS OK FROM METER TO WATER HEATER AND GROUND MOUNTED EXTERIOR UNIT. ALL CORRECTIONS MADE. |
| 10/24/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PLEASE PROVIDE #18 INSULATED TRACER WIRE WITH PL5 UNDERGROUND PIPING TERMINATEING 12" ABOVE GROUND ON EACH END 2) ALL ABOVE GROUND PIPING SHALL BE 6" MINIMUM FROM FINISHED GRADE 3) PLEASE CHECK FOR PROPER GROUNDING OF GAS SYSTEM. RETEST PIPING AND CALL FOR REINSPECTION |
| 10/22/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0920*/ PLEASE CALL FOR AN INSPECTION WHEN SOMEONE WILL BE HOME. |