Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03PL01686
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/05/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVES OK. 3) WATER HTR FLU VENT, T&P VALVE AND DRAIN IS OK. | |
11/04/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ 1) CAN NOT HAVE ANY UNIONS IN LINE. MUST USE RIGHT - LEFT HAND NIPPLES, SEE SEC. 1211.10 94 UPC. 2) MUST REMOVE ALL THREAD PROTEDTOR COUPLING IN LINE AND REPLACE WITH APPROVED COUPLINGS. 3) MUST SCREW DOWN FLU VENT FOR WATER HEATER WITH (3) SHEET METAL SCREWS PER JOINT AND AT APPLIANCE COLLAR. 4) MUST EXTEND WATER HEATER FLU VENT 3' ABOVE COOLER WHEN VENT IS LOCATED WITHIN 10' OF COOLER. 5) RE-TEST THE SYSTEM 10 LBS MIN. |