Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/12/2003 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) GAS CARD DROPPED AT METER 2) 10 PSI PRESSURE TEST OK FROM METER TO STOVE WATER HEATER AND FURNACE |
| 11/07/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ SYSTEM MUST HOLD 10 PSI TEST. EXTEND WATER HEATER AND FURNACE VENT TO 3' ABOVE COOLER AND RE-INSTALL APPROVED GAS CAP. |
| 10/29/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 10/24/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 10/20/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PLEASE PROVIDE ACCESS TO ENTIRE GAS SYSTEM AT TIME OF NEXT INSPECTION. |
| 10/16/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ PLEASE PROVIDE ACCESS TO GAS SYSTEM AT TIME OF NEXT INSPECTION. |
| 10/15/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PLEASE PROVIDE THREAD PROTECTORS WITH COUPLINGS ON 1" AND 3/4" PIPING. 2) PLEASE PROVIDE 10 PSI TEST TO ENTIRE SYSTEM. 3) PLEASE PROVIDE CSA OR AGA APPROVED GAS VALVES AT ALL LOCATIONS FOR APPLIANCES. 4) PLEASE PRIME AND TAPE ALL PIPING AND FITTINGS UNDERGROUND. |