Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/02/2003 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 10/30/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) ABS REQUIRES AT LEAST 12" OF COVER. 2) ABS MAY NOT BE INSTALLED IN EXPOSED EXTERIOR LOCATIONS. 3) A VENT MUST RISE VERTICALLY AT LEAST 6" ABOVE OVERFLOW OF FIXTURE BEFORE OFFSETTING HORIZONTALLY. 4) DRAIN MUST HAVE 1/4" PITCH PER FOOT. 5) A SANTEE MAY NOT BE INSTALLED IN A HORIZONTAL POSITION. |