Permit: T03PL01614

Parcel: 132130490


Addresses:

1015 E BENSON HY


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03PL01614

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/16/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK. 2) ALL CORRECTIONS HAVE BEEN MADE.
10/01/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/1) MUST HAVE A LICENSED PLBG CONTRACTOR TO DO TEST AND ANY WORK ON GAS SYSTEM. 2) MUST PROVIDE AIR PRESSURE TEST ON SYSTEM 10 LBS MIN AT TIME OF INSPECTION. 3) MUST PROVIDE AGA OR CSA GAS SHUT OFF VALVES FOR ALL APPLIANCES THAT DO NOT HAVE THIS VALVE. 4) MUST SCREW DOWN FLU VENT CONNECTOR WITH (3) SHEET METAL SCREWS PER JOINT AND AT APPLIANCE COLLAR. 5) MUST USE A FITTING TEE FOR W.H. FLU VENT. 6) MUST REMOVE UNION IN LINE ON ROOF. 7) MUST SUPPORT EXISTING GAS LINE 1-1/2" ABOVE ROOF. 8) MUST PROVIDE AGA SHUT OFF VALVE FOR UNIT ON ROOF.