Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/01/2003 |
PLUMBING - FINAL |
|
Approved |
1) CORRECTIONS MADE OK. T&P RELIEF DRAIN TO OUTSIDE OK. 2) OK FOR GAS. 3) UCC LEFT AT METER.S.W. GAS 889-1888. |
| 09/30/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) T&P RELIEF DRAIN MAY NOT GO UP THRU THE ROOF-MUST BE GRAVITY DRAIN 2) T&P VALVE MUST HAVE PROBE INTO TANK, PRESSURE VALVE NOT APPROVED |