Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03PL01537
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/25/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ RPPBP INSTALL (2PLACES) OK. CERTIFICATION OK. | |
09/24/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/1) BOTH ASSEMBLIES MUST BE SUPPORTED IN AN APPROVED MANNER. 2) 009 AT COFFEE URN MUST HAVE A DRAIN PIPED TO AN INDIRECT WASTE RECEPTACLE. 3) CERTIFICATION OK. 4) THIS FINAL WILL BE SUBJECT TO C OF O PERMIT |