Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/03/2003 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVES OK. 3) ALL CORRECTIONS HAVE BEEN MADE. |
| 10/15/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) MUST PROVIDE AIR PRESSURE TEST OF 10 LBS MIN. AT TIME OF INSPECTION. 2) MUST REPLACE GAS SHUT OFF VALVES FOR KITCHEN RANGE AND WATER HEATER WITH AGA OR CSA VALVES. 3) T&P DRAIN FOR WATER HEATER CAN NOT HAVE FLEX LINE. 4) T&P DRAIN MUST TERMINATE 6" ABOVE GRADE POINTED DOWNWARD. 5) PROVIDE DOOR FOR WATER HEATER ENCLOSURE. |