Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/03/2003 |
PLUMBING - FINAL |
|
Approved |
1) ALL CORRECTIONS HAVE BEEN MADE |
| 12/02/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) MUST CUT OFF THE THREADED END OF PIPE FOR T&P DRAIN 6" A.F.F. 2) MUST REMOVE UNION IN ½ GAS LINE FOR WTR HTR SUPPLY AND PROVIDE A RIGHT AND LEFT HAND NIPPLE. 3) MUST LOCATE SHUT OFF FIRST THAN UNION. 4) MUST PROVIDE SHUT OFF VALVE FOR WTR HTR WHERE FLEX CONNECTOR STARTS. 5) MAKE SURE ALL SHUT OFF VALVES ARE CLOSED AND RE-TEST SYSTEM. 10 LBS MIN. |
| 11/28/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 11/21/2003 |
PLUMBING - FINAL |
|
Denied |