Permit: T03PL01391

Parcel: 120083310


Addresses:

310 W MISSOURI ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/03/2003 PLUMBING - FINAL Approved 1) ALL CORRECTIONS HAVE BEEN MADE
12/02/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) MUST CUT OFF THE THREADED END OF PIPE FOR T&P DRAIN 6" A.F.F. 2) MUST REMOVE UNION IN ½ GAS LINE FOR WTR HTR SUPPLY AND PROVIDE A RIGHT AND LEFT HAND NIPPLE. 3) MUST LOCATE SHUT OFF FIRST THAN UNION. 4) MUST PROVIDE SHUT OFF VALVE FOR WTR HTR WHERE FLEX CONNECTOR STARTS. 5) MAKE SURE ALL SHUT OFF VALVES ARE CLOSED AND RE-TEST SYSTEM. 10 LBS MIN.
11/28/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*
11/21/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) MUST PROVIDE AGA OR CSA GAS SHUT OFF VALVES FOR ALL APPLIANCES. 2) MUST EXTEND T&P DRAIN AND TERMINATE 6" ABOVE FLOOR. 3) MUST REMOVE UNION IN LINE FOR WTR HTR 4) MUST SECURE ½" GAS LINE TO WTR HTR. 5) MUST PROVIDE AIR PRESSURE TEST ON ENTIRE SYSTEM.