Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T03PL01384
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/03/2003 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK 2) GAS SHUT OFF VALVES OK 3) WATER HEATER FLUE VENT, T & P VALVE AND DRSIN IS OK 4) FURNACE FLUE VENT IS OK | |
08/29/2003 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*/ SEE NOTES # 1&2 AS REQUESTED FROM LAST INSP. DATED 08/26/2003 | |
08/26/2003 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*/1) MUST PROVIDE A 10X10 LOUVER GRILL LOCATED 12" BELOW CEILING FOR WATER HEATER COMBUSTION RELIEF. 2) MUST PROPERLY SEAL AND VENT SLEEVE FOR EXISTING GAS LINE UNDER SLAB AND PORCH. 3) MUST HARD PIPE FURNACE THRU APPLIANCE HOUSING SEE SECTION 1212.0 SUB NOTE #2 - 94 UPC. |