Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/29/2003 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/24/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) MUST REMOVE UNION IN LINE AND REPLACE WITH RIGHT AND LEFT HAND NIPPLE. 2) MUST REMOVE FLEX LINE IN T&P DRAIN AND RUN 3/4" FULL SIZE TO EXISTING DRAIN. 3) MUST SCREW DOWN WATER HEATER VENT CONNECTOR WITH 3 SHEET METAL SCREWS PER JOINT AND AN APPLIANCE COLLAR. 4) MUST SEAL GAS LINE PENETRATION. 5) RETEST SYSTEM. |
| 09/11/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999* |