Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/30/2003 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/28/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ PLEASE PROVIDE SIGNITURE FROM BLD OFFICIAL ON APPEAL FROM AND RETURN TO JOB AT TIME OF NEXT INSP. |
| 10/23/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PLEASE PROVIDE ? OF APPEAL FOR WATER HEATERS, AS NEEDED 2) PLEASE SEE SECTION 608.5 RELIEF LINES. SECTION HOW TO TERMINATE |
| 10/20/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PLEASE PROVIDE ALL PAPERWORK. APPEAL NEEDED FOR WATER HEATERS AND COMPLETE JOB |
| 10/13/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ UNIT A - NEED PETITION OF APPEAL FOR ALTERNATE MEANS OF T&P - ALSO PLEASE INSTALL SCREWS AT ALL VENT JOINTS AND PROVIDE 1" CLEARANCE AT VENT THRU CEILING. UNIT B - NEEDS T&P DRAIN COMPLETED TO DAYLIGHT. UNIT C - WATER HEATER IS EXISTING. UNIT D - WATER HEATER IS EXISTING. |