Permit: T03PL01313

Parcel: 118050320

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
06/08/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*/ ALL CORRECTIONS HAVE BEEN MADE,
06/01/2004 PLUMBING - GAS PRESSURE TEST Denied 1) MUST REMOVE THREAD PROTECTOR COUPLING AND REPLACE WITH APPROVED BLK IRON COUPLINGS. 2) MUST APPLY APPROVED TAPE PRIMER ON ALL FITTINGS BELOW GROUND THEN APPLY 10 MIL TAPE. 3) MUST REMOVE UNION IN LINE AND USE RIGHT/LEFT HAND NIPPLE. 4) MUST REMOVE ½" SPRINKLER 90o AND REPLACE WITH APPROVED BLK STEEL MALABLE 90o. 5) MUST STRAP DOWN ½" GAS DROP AT FURNACE. 6) MUST INSTALL VENT CONNECTOR TO WTR HTR AND SCREW DOWN WITH 3 SHEET METAL SCREWS PER JOINT. 7) RETEST THE SYSTEM.