Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/14/2003 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VAVLES OK. 3) WATER HEATER T&P VALVE AND DRAIN IS OK. |
| 08/13/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) MUST PROVIDE AIR PRESSURE TEST ON SYSTEM 10LBS MIN. AT TIME OF INSPECTION. 2) MUST LOCATE THE UNION DOWNSTREAM OF SHUT OFF VALVE, NOT UPSTREAM. 3) MUST EXTEND T&P DRAIN TO DAYLIGHT. 4) ELECTRICAL CONNECTION TO WATER HEATER HAS SEVERAL VIOLATIONS. HAVE A LICENSED ELECTRICIAN ADDRESS THIS. |
| 08/08/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) MUST HAVE A LICENSED PLUMBING CONTRACTOR TO DO ANY WORK ON GAS SYSTEM. PLEASE PROVIDE THIS INFORMATION AT TIME OF INSPECTION 2) MUST PROVIDE AIR PRESSURE TEST ON SYSTEM AND BRING SYSTEM TO CURRENT CODE |