Permit: T03PL01286

Parcel: 136211150


Addresses:

7451 E BROOKS DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/08/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK 2) GAS SHUT OFF VALVES OK 3) WATER HEATER FLU VENT, P & T VALVE AND DRAIN IS OK 4) FURNACE FLU VENT OK 5) OK TO BACKFILL TRENCH
08/06/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/1) MUST REMOVE THREAD PROTECTORS IN GAS LINE UNDERGROUND AND REPLACE WITH APPROVED COUPLINGS. 2) MUST APPLY TAPE PRIMER (YELLOW) THEN APPLY 10 - MIL TAPE TO JOINTS UNDERGROUND AND WRENCH MARKS. 3) MUST PROVIDE AIR PRESSURE TEST OF 10 LBS MIN @ TIME OF INSPECTION. 4) MUST HARD PIPE THROUGH FURNACE HOUSING THEN CONNECT FLEX CONNECTOR. 5) REPLACE FURNACE GAS VAVLE WITH AGA OR CSA GAS SHUT OFF VALVE.