Permit: T03PL01229

Parcel: 128110610


Addresses:

5003 E JULIA ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/22/2003 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
08/14/2003 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*/1) MUST PROVIDE VARIENCE FORM FOR ALTERNATE METHOD OF INSTALLATION OF T&P DRAIN. THIS FORM MUST BE SIGNED BY HOMEOWNER AND CODES ADMINISTRATOR AND COPY OF FORM ON SITE AT TIME OF INSPECTION. 2) MUST PROVIDE A FACTORY PRESET PRESSURE REFIFE(?) VALVE @ 125 PSI. 3) T&P DRAIN CAN NOT CONNECT WITH CONDENSATE DRAIN. 4) MUST PROVIDE (3) SHEET METAL SCREWS PER JOINT FOR WATER HEATER VENT CONNECTOR AND APPLIANCE COLLAR. 5) GAS PRESSURE TEST IS OK.