Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK 2) GAS SHUT OFF VALVES-OK 3) WATER HEATER FLU VENT, P & T VALVE AND DRAIN IS OK 4) OK TO BACKFILL TRENCH 5) NOTE: GAS FURNACE HAS BEEN ELIMINATED |
|
| 07/23/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1) MUST PROVIDE AIR PRESSURE TEST OF 10 LBS MIN AT TIME OF INSP. 2) MUST SCREW DOWN WITH (3) SHEET METAL SCREWS PER JOINT @ WATER HTR, FLU VENT @ APPLIANCE COLLER AND ADJUSTABLE 90o. 3) MUST SEAL PENETRATIONS @ WALL GAS & P&T DRAIN. | |
| 07/22/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ NO ONE HOME |