Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2003 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection 0000*1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVES OK. 3) WATER HEATER FLU VENT IS OK, P&T VALVE & DRAIN IS OK.4)FURNACE FLU VENT IS OK |
| 07/22/2003 |
PLUMBING - GAS PRESSURE TEST |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) REMOVE UNION AND REPLACE WITH RIGHT AND LEFT HAND NIPPLE. 2) RETEST SYSTEM. 3) OK TO BACKFILL TRENCH. 4) EXTEND SINGLE WALL FLU VENT @ WATER HTR. 5) STRAP DOWN 3/4 GAS LINE. |
| 07/15/2003 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
1) SYSTEM NOT HOLDING TEST. 2) WATER HTR P&T DRAIN CANNOT HAVE FLEX LINE. MUST BE 3/4 FULL SIZE ALL THE WAY. 3) MUST REPLACE P&T VALVE @ WATER HTR. 4) MUST PROVIDE A AGA OR CSA APPROVED SHUT OFF VALVE BEFORE THE UNION @ HOUSE CONNECTION. 5) RE TEST SYSTEM 10 LBS MIN. |