Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03PL01128
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/10/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
07/08/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1) WATER HTR FLU VENT MUST EXTEND 3'0" ABOVE COOLER WHEN VENT IS LOCATED WITHIN 10' OF COOLER. SEE SEC. 517-6 94 UPC. 2) MUST PROVIDE A FLASHING FOR ALL ROOF PENETRATIONS. 3) MUST PROVIDE (3) SHEET METAL SCREENS PER JOINT ON WATER HTR FLU VENT. 4) RE TEST SYSTEM. |