Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/07/2003 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/03/2003 |
PLUMBING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) GAS PRESSURE TEST OK 2) GAS SHUT OFF VALVES OK 3) OK TO BACKFILL TRENCH |
| 07/02/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) MUST EXTEND WATER HEATER FLU VENT 3'-0" ABOVE COOLER WHEN FLUR VENT IS LOCATED WITHIN 10' OF AIR INLET SEE SECTION: 517.6 94 UPC 2) CANNOT HAVE ANY TRAPED WATER ON P&T DRAIN 3) CAN NOT LOCATE GAS LINE ON FLOOR. MUST BE MINIMUM 6" ABOVE FINISH FLOOR SEE SECTION 1211.3 94 UPC |