Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03PL01090
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/30/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) OVER HEAD WATER DISTRIBUTION IS OK 2) OK FOR DRYWALL |