Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03PL01083
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
02/18/2004 | PLUMBING - FINAL | Not ready for Inspection | 1) PIPING TO BE PRIMED THEN TAPED TO 6" ABOVE FINISH GRADE. METALLIC GAS PIPING TO HAVE 12" MIN. COVER. 2) METALLIC TO PLASTIC TO HAVE 30" MIN. HORIZONTAL PIPING IN GROUND. 3) BLDG GAS PIPING TO BE PROPERLY BONDED. 4) PROVIDE ACCESS TO ENTIRE GAS SYSTEM. | |
01/23/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 10 PSI TEST MIN. FOR INSPECTION. COMPLETE WORK AND RECALL FOR INSPECTION. | |
01/22/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ PLEASE HAVE SOMEONE PRESENT AT TIME OF NEXT INSPECTION TO PROVIDE ACCESS. |