Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ALL APPLIANCES MUST BE CODE COMPLIANT RETEST ENTIRE SYSTEM UNCOVER ALL PIPE |
|
| 08/20/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/1) RENT UNIT NEEDS TO PROVIDE LICENSED CONTRACTOR. CODE VIOLATIONS ON WATER HEATER. 2) SEE CHAPTER #5 FOR PROPER CLEARANCES. ALSO TERMINATION OF RELIEF LINE. 3) CODE VIOLATION ON WALL HEATER LOCATION OF VALVE. 4) REMOVE UNIONS, PROVIDE COUPLINGS - AS PER LAST REQUEST ANCHOR ALL GAS LINES SEC 1/2 TO RANGE. 5) SEE SEC. 94 CODE 517.2 FOR VENT ON WATER HEATER. READ OVER LAST INSP. REQUEST. | |
| 08/19/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/1) MUST REMOVE THREAD PROTECTORS COUPLINGS AND REPLACE WITH APPROVED COUPLINGS AND RE-TAPE AND RE-TEST SYSTEM. SEE NOTE #2 FROM 7/7/03. 2) NO ONE HOME. I MUST HAVE ACCESS TO ALL APPLIANCES INSIDE THE HOUSE. | |
| 07/07/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 20 PSI TEST 1)PROVIDE MIN 1" CLEARANCE AROUND WATER HEATER VENT PIPE. REMOVE THREADS FROM BOTTOM OF T&P DRAIN PIPE. REPLACE T&P RELIEF VALVE. VENT PIPE ON WATER HEATER IS UPSIDE DOWN. CUT OFF ABANDONED GAS LINE IN WATER HEATER ROOM. 2) REMOVE THREAD PROTECTORS FROM GAS LINE & USE APPROVED COUPLINGS. 3) PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS. BLOCK & CLAMP GAS LINE. 4) CONNECT GAS LINE TO WALL HEATER. SECURE GAS PIPE TO WALL. RETEST SYSTEM. |