Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T03PL00983
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/30/2003 | PLUMBING - GAS PRESSURE TEST | Approved | ||
06/24/2003 | PLUMBING - GAS PRESSURE TEST | Denied | 1) CANNOT HAVE A UNION IN LINE WITHOUT A AGA OR CSA GAS SHUT OFF VALVE. 2) IF YOU CAN TEST UP TO BOILER GAS SHUT OFF VALVE THAN CONNECT 11/2" GAS SUPPLY DIRECT TO VALVE WITHOUT THE UNION 3) RE TEST SYSTEM | |
06/12/2003 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*/ 1) MUST USE REQUIRED TEST GAUGE FOR LOW PRESSURE GAS AND SYSTEMS REQUIRING 10 POUNDS OR LESS 2) I WILL NOT ACCEPT ANY GAS PIPING WITHOUT MARKINGS ON PIPE |