Permit: T03PL00958

Parcel: 130181540

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/31/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 10 PSI TEST IS OK FROM METER TO WALL FURNACE AND STOVE AND WATER HEATER. ALL CORRECTIONS MADE. GAS CARD DROPPED AT METER.
10/17/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) NO UNION SHALL BE ALLOWED IN GAS LINE AT METER LOCATION OR AT WATER HEATER LOCATION. 2) 10 PSI TEST SHALL HOLD FOR 15 MIN. 3) GAS PIPELINE SHALL BE 6" MIN. ABOVE FINISHED GRADE. 4) WATER HEATER MUST HAVE VENT THRU ROOF WITH APPROVED CAP. 5) PLEASE PROVIDE AGA OR CSA APPROVED GAS VALVE AT STOVE AND WATER HEATER AND FURNACE. 6) PLEASE PROVIDE PERMIT FOR NEW WATER HEATER. 7) TERMINATE T&P WITHIN 6" OF FINISHED GRADE.