Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
| 07/07/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 10 PSI TEST IS OK 1)PROVIDE MIN 1" CLEARANCE WHERE WALL HEATER VENT PIPE PENETRATES THE ROOF. 2) CONNECT VENT TO WATER HEATER. PROVIDE MIN 3 SCREWS PER JOINT. 3) PROVIDE T&P DRAIN TO WITHIN 6" OF GROUND. 4) EXTEND WATER HEATER VENT 2' ABOVE ROOF. 5) WALL HEATER VENT CANNOT TRANSITION FROM DOUBLE WALL PIPE TO SINGLE WALL PIPE AT ROOF PENETRATOR. PROVIDE AN APPROVED CAP. |