Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2003 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* | |
| 06/05/2003 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*/ 1) 20 PSI TEST IS OK 2) WATER HEATER VENT IS INSTALLED UPSIDEDOWN 3) PROVIDE MINIMUM 1" CLEARANCE FROM ROOFING AND TAR WHERE VENT PENETRATES 4) THE ROOF FROM WATER HEATER ROOM SCREW VENT TO WATER HEATER CHAFT DIVERTER | |
| 05/16/2003 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*EVERYTHING INSIDE HOUSE IS OK 1.) PROVIDE A T & P DRAIN LINE TO WITHIN 6" OF GROUND 2.) PROVIDE 3 SCREWS IN EACH JOINT ON WATER HEATER VENT CONNECTOR. 3.) PROVIDE MIN 1" CLEARANCE AROUND VENT PIPE. VENT PIPE MUST BE MIN 5' IN LENGTH FROM DRAFT DIVERTER TO BOTTOM OF CAP. 4.) PROVIDE ROOF JACKS AT ROOF PENETRATIONS. RETEST SYSTEM. RECALL FOR INSPECTIONS. OK TO ACCESS BACK YARD TO WATER HEATER. |
|
| 05/15/2003 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0920* |