Permit: T03PL00848

Parcel: 135050350

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/17/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) CANNOT CHOKE SUPPLY AND OUTLET TO WATER SOFTENER THIS SUPPLY MUST BE THE SAME SIZE AS HOUSE SUPPLY SEE SECTION: 610.2 94 UPC 2) DISCHARGE DRAIN FOR SOFTENER CAN NOT CONNECT INTO BLDG SEWER SEE SECTION: 602.4
07/11/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) NO ONE HOME 12:35 PM