Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/08/2003 |
PLUMBING - GAS PRESS TEST FNL |
|
Approved |
IVRS - Inspection 0000* |
| 06/24/2003 |
PLUMBING - GAS PRESS TEST FNL |
|
Denied |
IVRS - Inspection 0999*/ 1) STOVE FLEX LINE MUST BE INCLUDED IN THIS TEST. WITH THE VALVE INSTALLED 2) WATER HEATER: CANNOT USE 2 FLEX LINES SPLICED. INSTALL VALVE ON METALLIC PIPING 3) CONNECT FLUE VENT CONNECTOR TO WATER HEATER 4) INSTALL DISCHARGE LINE ON TPRV 5) REMOVE DUCT TAPE FROM DRYER VENT PIPING AT JOINT OF SINGLE WALL TO DOUBLE WALL PIPE 6) NEED 1" MIN CLEARANCE AROUND DRYER VENT PIPE THRU ROOF |
| 06/20/2003 |
PLUMBING - GAS PRESS TEST FNL |
|
Denied |
IVRS - Inspection 0999*/ 1) CALLED 795-6950 AT 9:30 AM, 10;15 AM AND 12"30 AM. LET IT RING 10 TIMES EACH CALL. NO ANSWER. WENT BY THE PROPERTY, NO ONE THERE |