Permit: T03PL00691

Parcel: 137100250


Addresses:

727 W NEBRASKA ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/19/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*
1.) GAS PRESSURE TEST IS OK
2.) GAS SHUT OFF VALVES OK
3.) WATER HTR FLU VENT, P & T VALVE & DRAIN IS OK
4.) OK TO BACKFILL TRENCH.
04/18/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) MUST PROVIDE AIR PRESSURE TEST ON ENTIRE SYSTEM.
2.) MUST CONNECT NEW GAS TO EXSISTING GAS LINE
3.) P & T DRAIN HAS LEAK @ UNION
4.) MUST VERIFY THAT P & T VAVLES PROBE GOES INTO WATER HTR TANK MIN 2".
5.) RE TEST SYSTEM 10LBS MIN.